Saturn
Enterprises, Inc.
|
![]() |
Leading Supplier of HVAC Products for the Global Market |
![]() |
||||||||||||||||
| The
Jones Residence |
||||||||||||||||
| Problem: | ||||||||||||||||
|
The HVAC system for the Jones Residence has 2 chillers with six fans. The town of Greenwich, Connecticut has a city ordinance stating that the allowable noise level at the property line is 55 dBA from 7:00 a.m. to 10:00 p.m. and 49 dBA from 10:01 p.m. to 6:59 a.m. During a sound test by the city, the residence was found to have the following levels: |
||||||||||||||||
|
||||||||||||||||
| The city then ascertained that the residence did not comply with the allowable noise levels and that action must be taken to correct the problem. | ||||||||||||||||
|
Solution:
|
||||||||||||||||
![]() |
||||||||||||||||
| RINK Sound Control designed an
enclosure that would attenuate the noise produced by 1 Compressor and
6 Fans running at once down to 50 dBA as per the customer's request. The
design consisted of an enclosure constructed of RINK LAS-4 Acoustical
Louvers and a roof of RINK 2" panels mounted on top of each chiller
in a penthouse fashion. After the treatment was completed, the new sound
levels at the property line were measured as such: |
||||||||||||||||
|
||||||||||||||||
|
|
||||||||||||||||
Home | Brands | New Products | Links | Policies | Downloads | Contact Us | Espanol